PW LADDER TRAY W*=Nominal Tray Width H*=Tray Side Rail Height Wall Firestop Sleeve Example 0440 product used as a wall sleeve per UL assembly W-L-3226 and C-AJ-3232 Wall Assembly (Gypsum Wall Shown) AdjustableCollar Hilti Fire Blocks Hilti Fire Blocks Cables Cables Wall Assembly (Gypsum Wall Shown) AdjustableCollar Penetration Sleeve Penetration Sleeve Floor Assembly Floor Assembly W*=Nominal Tray Width H*=Tray Side Rail Height Floor Firestop Sleeve Example 0440 product used as a floor sleeve per UL assembly F-A-3022 Hilti Fire Blocks Hilti Fire Blocks Cables Cables Fixed Collar Fixed Collar Adjustable Collar Fixed Collar Fixed Collar Wall Anchors (Not Included) Wall Anchors (Not Included) Adjustable Collar Masonry Anchors (Not Included) Penetration Sleeve Penetration Sleeve Masonry Anchors (Not Included) WALL/FLOOR SLEEVE DESCRIPTION Designed for single runs of cable tray, having a height and width to match the tray system specified. One end of the 20 inch sleeve has a flange attached 6 inches from the end, while the flange for the other end is " floating " and is free to slide directly against the face of the wall as needed. The 20 inch length of the sleeve will accommodate a wall thickness of up to 8 inches. A wall thickness of 8 inches will result in the sleeve protruding 6 inches from each side of the wall. Both ends of the sleeve are punched with holes for attaching cable tray splice plates or hardware needed for the tray system specified. INSTALLATION The opening in the wall should be within 1 inch of the nominal height and width of the cable tray. The flanges of the sleeve have 7/16 " diameter mounting holes for attachment to the wall using 3/8 " diameter hardware. Hardware for wall attachment is not included. After the sleeve is mounted in the wall or floor, the cable trays on either side of the sleeve can be connected using the hardware supplied with the sleeve. When the trays are in place, the cables should be pulled through the wall and sleeve as needed. After all of the cables are installed in the tray, install the Fire Blocks as described. Any voids between cables should be filled with the Firestop Putty Stick / Sealant. TECHNICAL DATA Construction ............ Arc Welded Sleeve Dimensions .............. 20 " x Tray Width x Tray Height Flange Dimensions .............. (Tray Width + 6 " ) x (Tray Height + 6 " ) UL Classification ...... Qualifies for use as an equipment grounding conductor per N.E.C. 392.7. Cross-sectional area and amperage ratings are based on the cable tray system attached to the sleeve. FIRE BLOCKS INSTALLATION Walls: Fire Blocks shall be installed with 5 " dimension projecting through and centered within wall assembly. Floors: Fire Blocks shall be installed with 5 " dimension projecting through opening, flush with the top surface of sleeve or recessed within sleeve at any level above the top surface of floor. Fire blocks fill the annular space between the cables and the sleeve. Fire Blocks may be cut to match the profile of cables or to fit opening. Any voids should be filled with 0618 Firestop Putty Stick / Sealant. WALL PENETRATION SLEEVE CATALOG NUMBERING EXAMPLE: CONNECTOR SYSTEM NO. 6 M 2 -0440-36- G E PRODUCT NO. SIDE RAIL HEIGHT 4 - 4 " 5 - 5 " 6 - 6 " 7 - 7 " MATERIAL M G T FITTING SERIES This item must be specified as SERIES2 (S2) WIDTH 06 - 6 " 09 - 9 " 12 - 12 " 18 - 18 " 24 - 24 " 30 - 30 " 36 - 36 " For detailed material and finish descriptions, see page B.6. FASTENER OPTIONS GE S6 B.69 WWW.LEGRAND.US/CABLOFIL METALLIC FIRESTOP SYSTEMShttp://WWW.LEGRAND.US/CABLOFIL