PW LADDER TRAY CABLE CLEAT SPACING Cablofil recommends 3' linear spacing between cable cleats. If a spacing of greater than 3' is requested, please contact Cablofil's tech support team at technical.support-CAB@legrand.us and provide the peak fault of the circuit. CCT1 SINGLE CABLE SHORT CIRCUIT TESTING TO IEC 61914 - CLAUSE 9.5 PARALLEL FORMATION One short circuit 600mm fixed cleat centres 38mm 0.1 sec 155kA Peak 738kA r.m.s CCT3 THREE CABLES SHORT CIRCUIT TESTING TO IEC 61914 - CLAUSE 9.5 One short circuit 300mm fixed cleat centres 0.1 sec 140kA Peak 63.6kA r.m.s One short circuit 600mm fixed cleat centres 0.1 sec 109kA Peak 51.9kA r.m.s Two short circuits 600mm fixed cleat centres 0.1 sec 109kA Peak 51.9kA r.m.s Two short circuits 300mm fixed cleat centres 0.1 sec 135kA Peak 61.4kA r.m.s One short circuit 600mm fixed cleat centres 1 sec 75.1kA Peak 35.7kA r.m.s One short circuit 300mm fixed cleat centres 1 sec 80.1kA Peak 38.5kA r.m.s Two short circuits 300mm fixed cleat centres 1 sec 74.8kA Peak 35.6kA r.m.s One short circuit 600mm fixed cleat centres 38mm 1 sec 80.8kA Peak 38.5kA r.m.s Two short circuits 600mm fixed cleat centres 38mm 0.1 sec 154.3kA Peak 73.5kA r.m.s Two short circuits 600mm fixed cleat centres 38mm 1 sec 80.8kA Peak 38.5kA r.m.s MULTICONDUCTOR FORMATION One short circuit 600mm fixed cleat centres 62.6mm 0.1 sec 129kA Peak 58.6kA r.m.s Two short circuits 600mm fixed cleat centres 62.6mm 0.1 sec 120kA Peak 54.5kA r.m.s CCT4 FOUR CABLES SHORT CIRCUIT TESTING TO IEC 61914 - CLAUSE 9.5 One short circuit 300mm fixed cleat centres 0.1 sec 152kA Peak 69.1kA r.m.s Two short circuits 300mm fixed cleat centres 0.1 sec 138kA Peak 62.7kA r.m.s One short circuit 600mm fixed cleat centres 0.1 sec 130.4kA Peak 59.3kA r.m.s Two short circuits 600mm fixed cleat centres 0.1 sec 120.4kA Peak 54.7kA r.m.s One short circuit 300mm fixed cleat centres 1 sec 82kA Peak 40.2kA r.m.s B.89 WWW.LEGRAND.US/CABLOFIL CABLE CLEATShttp://WWW.LEGRAND.US/CABLOFIL