WIREMOLD / INFLOOR SYSTEMS WALKERCELL® Raceway Type WCR11/2 WCR2 WCR3 Raceway Type WCR11/2 WCR2 WCR3 Cell/Duct Capacity Sq. In. 8.2 11 18.8 Cell/Duct Capacity Sq. In. 8.2 11 18.8 CELLULAR RACEWAY SYSTEMS Walkercell Communications Wire Fill Capacity* Unshielded Twisted Pair 4-pair, 4-pair, 24 AWG, Cat 5 0.038 85 115 197 TYPE 1 0.119 27 37 63 4-pair, 24 AWG, Cat 6 24 AWG, Cat 6a 0.049 66 89 153 TYPE 2 0.17 19 26 44 0.098 34 44 76 Shielded Twisted Pair TYPE 3 0.047 69 93 159 2 Strand 0.025 130 173 296 4 Strand 0.028 116 155 264 *Capacities shown reflect 40% wire fill. Left and right channels are intended for communication wiring. Center channel is for power. Walkercell Power Wire Fill Capacity* Raceway Type Cell/Duct Capacity WCR11/2 WCR2 WCR3 Sq. In. 4.22 4.3 8.5 14 AWG 0.0097 168 172 351 2-pair, 24 AWG 0.015 217 285 488 Telephone 4-pair, 24 AWG 0.028 116 155 265 Coaxial 25-pair, 24 AWG 0.132 24 33 56 RG58/U 0.03 108 146 252 Fiber 6 Strand 0.035 93 127 216 Fiber ZipCord 0.01 326 463 791 RG59/U 0.046 70 96 162 RG6/U 0.057 57 77 130 12 AWG 0.0133 126 129 256 10 AWG 0.0211 80 82 161 8 AWG 0.0366 45 47 93 *Capacities shown reflect 40% wire fill. Left and right channels are intended for communication wiring. Center channel is for power. Walkercell Cellular Raceway Preset Selection Guide WCR11/2 WCR2 Minimum System Depth 3 1/2 " (89mm) Preset PK150 *1⁄8 " min. (3.2mm) Finished Floor 2 " (51mm) 1 1/2 " (38mm) OTHER SYSTEM DEPTHS FOR WCR11/2 SYSTEM DEPTH PRESET CAT. NO. 3 1/2 " 4 " 4 1/2 " 5 " 5 1/4 " 5 1/2 " (89mm) (102mm) (114mm) (127mm) (133mm) (140mm) PK150 PK200 PK250 PK300 PK325 PK350 FILL OVER CELL 2 " 2 1/2 " 3 " 3 1/2 " 3 3/4 " 4 " (51mm) (64mm) (76mm) (89mm) (95mm) (102mm) Minimum System Depth 3 1/2 " (89mm) Preset PK150 *1⁄8 " min. (3.2mm) Finished Floor 1 1⁄2 " (38mm) 2 " (51mm) OTHER SYSTEM DEPTHS FOR WCR2 SYSTEM DEPTH PRESET CAT. NO. 3 1/2 " 4 " 4 1/2 " 5 " 5 1/4 " 5 1/2 " (89mm) (102mm) (114mm) (127mm) (133mm) (140mm) PK150 PK200 PK250 PK300 PK325 PK350 FILL OVER CELL 1 1/2 " 2 " 2 1/2 " 3 " 3 1/4 " 3 1/2 " (38mm) (51mm) (64mm) (76mm) (83mm) (89mm) Recommend a minimum of 1/8 " (3.2mm) concrete over preset. * If concrete depth over preset is over 3/4 " (19.1mm) it may be difficult to break-out concrete and excessive spalling may occur. For system depth greater than above standard preset height use PK Extension Ring. *1⁄8 " min. (3.2mm) 6 AWG 0.0507 33 34 67 4 AWG 0.0824 20 21 41 WCR3 Minimum System Depth 4 1/2 " (114mm) Preset PK150 Finished Floor 1 1⁄2 " (38mm) 3 " (76mm) OTHER SYSTEM DEPTHS FOR WCR3 SYSTEM DEPTH PRESET CAT. NO. 4 1/2 " 5 " 5 1/2 " 6 " 6 1/4 " 6 1/2 " (114mm) (127mm) (140mm) (152mm) (159mm) (165mm) PK150 PK200 PK250 PK300 PK325 PK350 FILL OVER CELL 1 1/2 " 2 " 2 1/2 " 3 " 3 1/4 " 3 1/2 " (38mm) (51mm) (64mm) (76mm) (83mm) (89mm) WWW.LEGRAND.US/WIREMOLD 719 INFLOOR SYSTEMS INDEXhttp://WWW.LEGRAND.US/WIREMOLD