WIRE MESH TRAY WIRE MESH TRAY Quick Reference Load Table Use this handy load guide to determine the capacity of your cable pathway. Always plan for extra space in cable pathways during the initial installation to allow capacity for future cable additions. For information on other cable sizes, go to www.legrand.us/cablofil/tools and use our online load calculator. LOAD TABLE LOADS IN LBS/FT PER SPAN FILL AREA (sq. in.) 5 6 7 8 CF54/50(2x2) 4.03 32.0 15.1 11.1 9.1 CF54/100(2x4) 8.06 39.4 22.3 16.4 15.9 CF54/150(2x6) 12.09 46.5 27.6 20.3 19.1 CF54/200(2x8) 16.12 54.2 36.4 26.7 24.7 INTRODUCTION TRAY A.6 WWW.LEGRAND.US/CABLOFIL CF54/300(2x12) 24.18 71.6 47.1 34.6 31.7 CF54/450(2x18) 36.27 134.9 91.0 66.8 60.3 CF54/600(2x24) 48.36 119.4 95.4 70.1 62.8 CF105/100(4x4) 15.97 68.3 46.4 34.1 30.5 CF105/150(4x6) 23.95 98.4 60.2 44.3 40.9 CF105/200(4x8) 31.93 109.4 76.2 56.0 51.9 CF105/300(4x12) 47.90 142.0 126.8 93.1 89.2 CF105/450(4x18) 71.84 151.0 129.9 95.4 88.7 CF105/600(4x24) 95.79 151.0 129.9 95.4 88.7 CF150/150(6x6) 34.41 127.5 123.0 90.4 89.1 CF150/200(6x8) 45.88 127.5 123.0 90.4 89.1 CF150/300(6x12) 68.82 175.9 155.0 113.9 98.3 CF150/450(6x18) 103.23 175.9 155.0 113.9 98.3 CF150/600(6x24) 137.64 228.5 165.7 121.7 91.3 ZF150/900(6x36) 206.49 228.5 165.7 121.7 91.3http://www.legrand.us/cablofil/tools http://WWW.LEGRAND.US/CABLOFIL